Cells Per Unit | 6 |
Voltage Per Unit | 12 V |
Capacity | 18W @ 15min-rate to 1.67V per cell @25 (77 ) |
Weight | Approx. 1.53 kg (3.37lbs) |
Maximum Discharge current | 130A (5sec) |
Internal Resistance Approx. | Approx. 28.5mΩ |
Operating Temperature Range | Discharge:-15℃~50℃(5°F~122°F) Charge:-15℃~40℃(5°F~104°F) Storage:-15℃~40℃(5°F~104°F) |
Nominal Operating Temperature Range | 25℃±3℃ (77°F±5°F) |
Float charging voltage | 13.5 to 13.8 VDC/unit Average at 25℃ (77°F) |
Recommended Maximum Charging current limit | 1.8A |
Equalization and Cycle Service | 14.4 to 15.0 VDC/Unit Average at 25℃(77°F) |
Self Discharge | It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃ |
Terminal | F2-Faston Tab250 |
Container Material | ABS(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon request. |