Cells Per Unit | 6 |
Voltage Per Unit | 12 V |
Capacity | 65Ah @ 20 hr-rate to 1.75V per cell @ 25°C (77°F) |
Weight (kg) | Approx. 20.80kg. (45.9 lbs.) |
Maximum Discharge current (A) | 500A (5sec.) |
Internal Resistance Approx. (mΩ) | Approx. 5.3 mΩ |
Operating Temperature Range | Discharge:-15℃~50℃(5°F~122°F) Charge:-15℃~40℃(5°F~104°F) Storage:-15℃~40℃(5°F~104°F) |
Nominal Operating Temperature Range | 25°C ± 3°C (77°F ± 3°F) |
Float charging voltage | 13.5 to 13.8 VDC/unit Average at 25℃ (77°F ) |
Recommended Maximum Charging current limit | 19.5 A |
Equalization and Cycle Service | 14.4 to 14.5 VDC/unit Average at 25℃ (77°F ) |
Self Discharge | It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃ |
Terminal | I2-Thread lead alloy recessed terminal to accept M6 bolt |
Container Material | Polypropylene(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon request. |